The Estimation of the Influence of Each Harmonic Component in Load Unbalance of Distribution Transformers in Harmonic Loading Condition

Javad Behkesh Noshahr, Mehdi Bagheri, Mostafa Kermani

Research output: Chapter in Book/Report/Conference proceedingConference contribution

Abstract

Nowadays, due to their widespread utilization, transformers are considered as the main component of distribution networks. Despite the important role playing by transformers, some problems e.g. flow of high-range current from transformers' null despite balancing the currents of phases has been observed in the appropriate utilization of distribution transformers. This phenomenon is observed in most distribution stations. Although the presence of single- phase loads causes an unbalance in transformers; load displacement and network balancing lead again to the flow of huge current from transformers neutral. One of the its reasons can be the usage of distribution transformers in harmonic load condition, in three-phase distribution networks load current harmonics in transformers' neutral have negative considerable consequences. Therefore, it is required to evaluate and analyze the harmonic effects in the presence of nonlinear loads. since the harmonic component playing an important role in the creation of load unbalance, it is necessary to evaluate them; these components have considerable roles in the selection of compensation methods in the process of harmonic contamination especially the selection of compensator filters. In this paper, by Matlab/Simulink stimulation capability performed as real-time to examine the reasons for increased flow of neural coil of the transformer in a harmonic environment and evaluate the influence of each harmonic component of load flow in the creation of unbalance and neutral flow of transformer. The information of harmonic load includes the range of harmonic component and its angles from outflow current of a static transformer. The load's current has a harmonic component of 3, 5, 7, 9, 11, 13, 15 order in addition to range in main frequency (50Hz). The results show that the unbalance of the transformer's load in harmonic load condition has increased by 1.529%. In addition, the share of each harmonic component depends on their angle in addition to the range such that the impact on the main frequency is much higher than other harmonic components, which is due to asymmetry and phase difference between phases.

Original languageEnglish
Title of host publicationProceedings - 2019 IEEE International Conference on Environment and Electrical Engineering and 2019 IEEE Industrial and Commercial Power Systems Europe, EEEIC/I and CPS Europe 2019
PublisherInstitute of Electrical and Electronics Engineers Inc.
ISBN (Electronic)9781728106526
DOIs
Publication statusPublished - Jun 1 2019
Event19th IEEE International Conference on Environment and Electrical Engineering and 2019 IEEE Industrial and Commercial Power Systems Europe, EEEIC/I and CPS Europe 2019 - Genoa, Italy
Duration: Jun 11 2019Jun 14 2019

Publication series

NameProceedings - 2019 IEEE International Conference on Environment and Electrical Engineering and 2019 IEEE Industrial and Commercial Power Systems Europe, EEEIC/I and CPS Europe 2019

Conference

Conference19th IEEE International Conference on Environment and Electrical Engineering and 2019 IEEE Industrial and Commercial Power Systems Europe, EEEIC/I and CPS Europe 2019
CountryItaly
CityGenoa
Period6/11/196/14/19

Fingerprint

Transformer
Electric power distribution
Harmonic
Contamination
Distribution Network
Balancing
Influence
Range of data
Evaluate
Angle
Phase Difference
Matlab/Simulink
Compensator
Coil
Compensation and Redress
Asymmetry
Null

Keywords

  • Distribution transformer
  • Harmonic loading
  • Harmonic loads
  • Load unbalance
  • Null current

ASJC Scopus subject areas

  • Energy Engineering and Power Technology
  • Renewable Energy, Sustainability and the Environment
  • Electrical and Electronic Engineering
  • Industrial and Manufacturing Engineering
  • Environmental Engineering
  • Control and Optimization

Cite this

Noshahr, J. B., Bagheri, M., & Kermani, M. (2019). The Estimation of the Influence of Each Harmonic Component in Load Unbalance of Distribution Transformers in Harmonic Loading Condition. In Proceedings - 2019 IEEE International Conference on Environment and Electrical Engineering and 2019 IEEE Industrial and Commercial Power Systems Europe, EEEIC/I and CPS Europe 2019 [8783488] (Proceedings - 2019 IEEE International Conference on Environment and Electrical Engineering and 2019 IEEE Industrial and Commercial Power Systems Europe, EEEIC/I and CPS Europe 2019). Institute of Electrical and Electronics Engineers Inc.. https://doi.org/10.1109/EEEIC.2019.8783488

The Estimation of the Influence of Each Harmonic Component in Load Unbalance of Distribution Transformers in Harmonic Loading Condition. / Noshahr, Javad Behkesh; Bagheri, Mehdi; Kermani, Mostafa.

Proceedings - 2019 IEEE International Conference on Environment and Electrical Engineering and 2019 IEEE Industrial and Commercial Power Systems Europe, EEEIC/I and CPS Europe 2019. Institute of Electrical and Electronics Engineers Inc., 2019. 8783488 (Proceedings - 2019 IEEE International Conference on Environment and Electrical Engineering and 2019 IEEE Industrial and Commercial Power Systems Europe, EEEIC/I and CPS Europe 2019).

Research output: Chapter in Book/Report/Conference proceedingConference contribution

Noshahr, JB, Bagheri, M & Kermani, M 2019, The Estimation of the Influence of Each Harmonic Component in Load Unbalance of Distribution Transformers in Harmonic Loading Condition. in Proceedings - 2019 IEEE International Conference on Environment and Electrical Engineering and 2019 IEEE Industrial and Commercial Power Systems Europe, EEEIC/I and CPS Europe 2019., 8783488, Proceedings - 2019 IEEE International Conference on Environment and Electrical Engineering and 2019 IEEE Industrial and Commercial Power Systems Europe, EEEIC/I and CPS Europe 2019, Institute of Electrical and Electronics Engineers Inc., 19th IEEE International Conference on Environment and Electrical Engineering and 2019 IEEE Industrial and Commercial Power Systems Europe, EEEIC/I and CPS Europe 2019, Genoa, Italy, 6/11/19. https://doi.org/10.1109/EEEIC.2019.8783488
Noshahr JB, Bagheri M, Kermani M. The Estimation of the Influence of Each Harmonic Component in Load Unbalance of Distribution Transformers in Harmonic Loading Condition. In Proceedings - 2019 IEEE International Conference on Environment and Electrical Engineering and 2019 IEEE Industrial and Commercial Power Systems Europe, EEEIC/I and CPS Europe 2019. Institute of Electrical and Electronics Engineers Inc. 2019. 8783488. (Proceedings - 2019 IEEE International Conference on Environment and Electrical Engineering and 2019 IEEE Industrial and Commercial Power Systems Europe, EEEIC/I and CPS Europe 2019). https://doi.org/10.1109/EEEIC.2019.8783488
Noshahr, Javad Behkesh ; Bagheri, Mehdi ; Kermani, Mostafa. / The Estimation of the Influence of Each Harmonic Component in Load Unbalance of Distribution Transformers in Harmonic Loading Condition. Proceedings - 2019 IEEE International Conference on Environment and Electrical Engineering and 2019 IEEE Industrial and Commercial Power Systems Europe, EEEIC/I and CPS Europe 2019. Institute of Electrical and Electronics Engineers Inc., 2019. (Proceedings - 2019 IEEE International Conference on Environment and Electrical Engineering and 2019 IEEE Industrial and Commercial Power Systems Europe, EEEIC/I and CPS Europe 2019).
@inproceedings{1c36de379be244309f430d6d567edbbb,
title = "The Estimation of the Influence of Each Harmonic Component in Load Unbalance of Distribution Transformers in Harmonic Loading Condition",
abstract = "Nowadays, due to their widespread utilization, transformers are considered as the main component of distribution networks. Despite the important role playing by transformers, some problems e.g. flow of high-range current from transformers' null despite balancing the currents of phases has been observed in the appropriate utilization of distribution transformers. This phenomenon is observed in most distribution stations. Although the presence of single- phase loads causes an unbalance in transformers; load displacement and network balancing lead again to the flow of huge current from transformers neutral. One of the its reasons can be the usage of distribution transformers in harmonic load condition, in three-phase distribution networks load current harmonics in transformers' neutral have negative considerable consequences. Therefore, it is required to evaluate and analyze the harmonic effects in the presence of nonlinear loads. since the harmonic component playing an important role in the creation of load unbalance, it is necessary to evaluate them; these components have considerable roles in the selection of compensation methods in the process of harmonic contamination especially the selection of compensator filters. In this paper, by Matlab/Simulink stimulation capability performed as real-time to examine the reasons for increased flow of neural coil of the transformer in a harmonic environment and evaluate the influence of each harmonic component of load flow in the creation of unbalance and neutral flow of transformer. The information of harmonic load includes the range of harmonic component and its angles from outflow current of a static transformer. The load's current has a harmonic component of 3, 5, 7, 9, 11, 13, 15 order in addition to range in main frequency (50Hz). The results show that the unbalance of the transformer's load in harmonic load condition has increased by 1.529{\%}. In addition, the share of each harmonic component depends on their angle in addition to the range such that the impact on the main frequency is much higher than other harmonic components, which is due to asymmetry and phase difference between phases.",
keywords = "Distribution transformer, Harmonic loading, Harmonic loads, Load unbalance, Null current",
author = "Noshahr, {Javad Behkesh} and Mehdi Bagheri and Mostafa Kermani",
year = "2019",
month = "6",
day = "1",
doi = "10.1109/EEEIC.2019.8783488",
language = "English",
series = "Proceedings - 2019 IEEE International Conference on Environment and Electrical Engineering and 2019 IEEE Industrial and Commercial Power Systems Europe, EEEIC/I and CPS Europe 2019",
publisher = "Institute of Electrical and Electronics Engineers Inc.",
booktitle = "Proceedings - 2019 IEEE International Conference on Environment and Electrical Engineering and 2019 IEEE Industrial and Commercial Power Systems Europe, EEEIC/I and CPS Europe 2019",
address = "United States",

}

TY - GEN

T1 - The Estimation of the Influence of Each Harmonic Component in Load Unbalance of Distribution Transformers in Harmonic Loading Condition

AU - Noshahr, Javad Behkesh

AU - Bagheri, Mehdi

AU - Kermani, Mostafa

PY - 2019/6/1

Y1 - 2019/6/1

N2 - Nowadays, due to their widespread utilization, transformers are considered as the main component of distribution networks. Despite the important role playing by transformers, some problems e.g. flow of high-range current from transformers' null despite balancing the currents of phases has been observed in the appropriate utilization of distribution transformers. This phenomenon is observed in most distribution stations. Although the presence of single- phase loads causes an unbalance in transformers; load displacement and network balancing lead again to the flow of huge current from transformers neutral. One of the its reasons can be the usage of distribution transformers in harmonic load condition, in three-phase distribution networks load current harmonics in transformers' neutral have negative considerable consequences. Therefore, it is required to evaluate and analyze the harmonic effects in the presence of nonlinear loads. since the harmonic component playing an important role in the creation of load unbalance, it is necessary to evaluate them; these components have considerable roles in the selection of compensation methods in the process of harmonic contamination especially the selection of compensator filters. In this paper, by Matlab/Simulink stimulation capability performed as real-time to examine the reasons for increased flow of neural coil of the transformer in a harmonic environment and evaluate the influence of each harmonic component of load flow in the creation of unbalance and neutral flow of transformer. The information of harmonic load includes the range of harmonic component and its angles from outflow current of a static transformer. The load's current has a harmonic component of 3, 5, 7, 9, 11, 13, 15 order in addition to range in main frequency (50Hz). The results show that the unbalance of the transformer's load in harmonic load condition has increased by 1.529%. In addition, the share of each harmonic component depends on their angle in addition to the range such that the impact on the main frequency is much higher than other harmonic components, which is due to asymmetry and phase difference between phases.

AB - Nowadays, due to their widespread utilization, transformers are considered as the main component of distribution networks. Despite the important role playing by transformers, some problems e.g. flow of high-range current from transformers' null despite balancing the currents of phases has been observed in the appropriate utilization of distribution transformers. This phenomenon is observed in most distribution stations. Although the presence of single- phase loads causes an unbalance in transformers; load displacement and network balancing lead again to the flow of huge current from transformers neutral. One of the its reasons can be the usage of distribution transformers in harmonic load condition, in three-phase distribution networks load current harmonics in transformers' neutral have negative considerable consequences. Therefore, it is required to evaluate and analyze the harmonic effects in the presence of nonlinear loads. since the harmonic component playing an important role in the creation of load unbalance, it is necessary to evaluate them; these components have considerable roles in the selection of compensation methods in the process of harmonic contamination especially the selection of compensator filters. In this paper, by Matlab/Simulink stimulation capability performed as real-time to examine the reasons for increased flow of neural coil of the transformer in a harmonic environment and evaluate the influence of each harmonic component of load flow in the creation of unbalance and neutral flow of transformer. The information of harmonic load includes the range of harmonic component and its angles from outflow current of a static transformer. The load's current has a harmonic component of 3, 5, 7, 9, 11, 13, 15 order in addition to range in main frequency (50Hz). The results show that the unbalance of the transformer's load in harmonic load condition has increased by 1.529%. In addition, the share of each harmonic component depends on their angle in addition to the range such that the impact on the main frequency is much higher than other harmonic components, which is due to asymmetry and phase difference between phases.

KW - Distribution transformer

KW - Harmonic loading

KW - Harmonic loads

KW - Load unbalance

KW - Null current

UR - http://www.scopus.com/inward/record.url?scp=85070826036&partnerID=8YFLogxK

UR - http://www.scopus.com/inward/citedby.url?scp=85070826036&partnerID=8YFLogxK

U2 - 10.1109/EEEIC.2019.8783488

DO - 10.1109/EEEIC.2019.8783488

M3 - Conference contribution

T3 - Proceedings - 2019 IEEE International Conference on Environment and Electrical Engineering and 2019 IEEE Industrial and Commercial Power Systems Europe, EEEIC/I and CPS Europe 2019

BT - Proceedings - 2019 IEEE International Conference on Environment and Electrical Engineering and 2019 IEEE Industrial and Commercial Power Systems Europe, EEEIC/I and CPS Europe 2019

PB - Institute of Electrical and Electronics Engineers Inc.

ER -